Olympic Watthour Meter

Two Wire, 120 Volts to Neutral and Three Wire, 120 Volts to Neutral, 240 Volts Line to Line, Dual Meter


The Olympic meter is really two meters in one. One of the meters measures a two-wire, 120 volt to neutral circuit and the other measures a standard three-wire, 120 volts to neutral, 240 volts line-to-line service. It has very limited applications, but for those who need it, it saves buying a second meter at extra cost. It may also be used on a four-wire, three phase 120/208 or 120/240 system. The Plus and Plus IO versions of this meter are the only ones we make that are capable of reporting the power used on each phase of a three phase system. The meter consists of an electronics module, three current transformers (CTs) and two electro-mechanical counters that displays the accumulated power used.

Available Configurations
The Olympic meters are available in a variety of configurations. Check the options in the Part Numbering Guide at the bottom of this page for details.

Current Capabilities
Meters are rated by the maximum current that can flow through the current transformers.  Generally speaking, the meter should be rated at or above the rating of the breaker that will protect the circuit to be measured.   Meters using solid-core CTs are available in 20, 100 and 200 amp versions.  Meters using split-core CTs are available in 200, 500, 750, 1000 and 1500 amp versions. 

Resolution
Meters of 200 amps or less usually have a resolution of 0.1 kwh. Meters over 200 amps usually have a resolution of 1.0 kwh. A test mode forces a resolution of 0.01 kwh. Meters can be ordered with any of these reolutions or a special low current resolution of 0.01 kwh normal, 0.001 kwh (1 watthour) test.

Automatic Meter Reading (AMR)
In addition to stand-alone meters that must be manually read, the meter is available with the following AMR options.

KYZ Pulse - An optically isolated output toggles between open and closed every time the counter advances.  These meters are frequently used with radio data collection systems in apartment buildings.

50ms Pulse - An optically isolated output that closes for 50ms then opens every time the counter advances.

Dedicated Twisted Pair - A local meter network that communicates over a twisted pair of wires.  Any number of meters can be connected to an RS-232 interface.  The RS-232 interface can be connected directly to a Windows compatible computer, to a telephone modem, or to a TCP/IP interface module.  You can use the free Microsoft Access application to read the meters or write your own custom application.  See the documentation section for more info.

Power Line Carrier - This system is the same as the Dedicated Twisted Pair except that communication is via the power line instead of separate wires.  Because of interference from nearby ground fault interrupters and switching power supplies, this system works best in marinas.

Enclosures
The Olympic meter is available in a variety of enclosures, either for a single meter or multiple meters.  See the enclosures page for more info.

OEM Versions
The Olympic meter is also available in an OEM version so that it can be installed in a third party NEMA enclosure.  This is usefull when the meters are to be installed in power pedestals in a marina or RV park.  A stainless steel mounting plate is available for mounting the display counters in the enclosure.

Alternate Configurations
The Olympic can also be used with just one or two CTs if desired.

Accuracy and Safety Certifications
Davidge Controls certifies that all our watthour meters meet or exceed the accuracy standards of ANSI C12.1(2001), the national standard for watthour meters that applies to all the utility companies in the country. 

All models of the Olympic meter carry an Underwriters Laboratories Recognized Component mark.

All models of the Olympic meter carry an Underwriters Laboratories Recognized Component mark.

Click on picture for larger view, then use browser's Back button to return here.

4320
4320 Meter

4720-4-3
Two solid core CTs

4735-1

Small Split-Core CT

4725-2

Large Split-Core CT
4921-1

Sealed Counter
4923-1

Unsealed Counter

Olympic Electronics Module Specifications
Voltage Requirements: 90-140 VAC Line to Neutral, 180-280 VAC Line to Line Physical Size: 5.0" x 2.78" x 0.91"
Frequency: 50-60 Hz Weight: 4.0 oz stand-alone, 4.3 oz Plus models
Power Consumption: less than 2 watts for stand-alone meters
less than 3 watts for Plus and Plus IO models
Operating Temp:
Note:
-20°F to 160°F (-28.8°C to 71.1°C)
Display counter range is smaller. See below.
Phase: Single phase or three phase Storage Temp: -40°F to 160°F (-40°C to 71.1°C)
Elements: One, two or three Humidity: Non-Condensing


Solid-Core Current Transformer Specifications
Model 4720/4  
Outside Diameter: 2.1" Turns Ratio: 400:1
Inside Diameter: 0.9" Burden Resistor: None - on circuit board
Weight 2.5 oz. Leads: 24";, 18 ga., 300V insulation


Split-Core Current Transformer Specifications
Model 4735/1  
Outside dimension: 3.3" x 2.2" Turns Ratio: 3000:1
Inside Dimemension: Burden resistor None - on circuit board
Weight: 12.4 oz. Leads: 68", 18 ga, 600V insulation
Model 4735/2  
Outside dimension: 4.5" x 4.2" Turns Ratio: 3000:1
Inside Dimemension: Burden resistor None - on circuit board
Weight: 22.2 oz. Leads: 68", 18 ga, 600V insulation


Electro-Mechanical Display Specifications
Sealed Counters  
Counter model: Kubler K46.20/K47.20 Panel Cutout: 1.06" x 0.55"
Operating Temp: 14°F (-10°C) - 140°F (60°C) Reset: None
Max dist from meter: 20 ft. for 12V counters
300 ft for 6V counters
Digits: 6 for 1.0 kwh and 0.1 kwh resolution
7 for 0.01 kwh resolution
  Wires to counters must be installed in conduit Digits for units are white, digits for tenths and hundredths are red


Olympic Part Numbering Guide
4 X 2 Y / Z  
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
  Z Part Number Suffix - Add values of desired features
0Solid Core CTs, 0.1 kwh resolution
150 ms pulse output when "X" =
1Twisted Pair Interrface for Plus IO meters
2KYZ pulse output when "X" =
23 multi-purpose IO ports for Plus IO meters
4Designates bi-directional Everglades Meter
81.0 kwh resolution
16Not used with this meter
320.01 kwh resolution
64Split-core CTs
1281 wh resolution available
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Y
0200 amp max
1100 amp max
320 amp max
5500 amp max
61500 amp max
7750 amp max
81000 amp max
| | 2 Two Counter Drivers
|
|
|
X
4Two Wire, 120 Volts to Neutral and Three Wire, 120 Volts to Neutral, 240 Volts Line to Line, Dual Meter

Example: 4320/11 means a Olympic meter, Two Wire, 120 Volts to Neutral and Three Wire, 120 Volts to Neutral, 240 Volts Line to Line, Dual Meter, triple-element, computer-readable, two counter drivers, 200 amps maximum, twisted pair interface, three bidirectional IO ports, 1.0 kwh resolution (Olympic Plus IO 200)