Glacier Watthour Meter

Two Wire, 208-240 Volts Line to Line


The Glacier meter is normally used to measure the power consumed by an appliance or piece of equipment, either 240 volts single phase or two legs of a 208 volt, three phase system where a neutral is not present. Do not use this meter if any part of the load uses 120 volts to neutral; use the Yosemite meter instead. The Glacier meter consists of an electronics module, one current transformer (CT) and an electro-mechanical counter that displays the accumulated power used. An enclosure is optional.

Available Configurations
The Glacier meters are available in a variety of configurations. Check the options in the Part Numbering Guide at the bottom of this page for details.

Current Capabilities
Meters are rated by the maximum current that can flow through the current transformers.  Generally speaking, the meter should be rated at or above the rating of the breaker that will protect the circuit to be measured.  Meters using solid-core CTs are available in 20, 100 and 200 amp versions.  Meters using split-core CTs are available in 200, 500, 750, 1000 and 1500 amp versions. 

Resolution
Glacier meters normally come with a resolution of 1.0 kilowatt hours (KWH). They may also be ordered with a resolution of 0.1 KWH or 0.01 KWH.

Automatic Meter Reading (AMR)
In addition to stand-alone meters that must be manually read, the meter is available with the following AMR options.

50ms Pulse - An optically isolated output that closes for 50ms then opens every time the counter advances. These meters are frequently used with radio data collection systems in apartment buildings.

Dedicated Twisted Pair - A local meter network that communicates over a twisted pair of wires.  Any number of meters can be connected to an RS-232 interface.  The RS-232 interface can be connected directly to a Windows compatible computer, to a telephone modem, or to a TCP/IP interface module.  You can use the free Microsoft Access application to read the meters or write your own custom application.  See the documentation section for more info.

Power Line Carrier - This system is the same as the Dedicated Twisted Pair except that communication is via the power line instead of separate wires.  Because of interference from nearby ground fault interrupters and switching power supplies, this system works best in marinas.

Enclosures
The Glacier meter is available in a variety of enclosures, either for a single meter or multiple meters.  See the enclosures page for more info.

OEM Versions
The Glacier meter is also available in an OEM version so that it can be installed in a third party NEMA enclosure.  This is usefull when the meters are to be installed in power pedestals in a marina or RV park.  A stainless steel mounting plate is available for mounting the display counters in the enclosure.

Accuracy and Safety Certifications
Davidge Controls certifies that all our watthour meters meet or exceed the accuracy standards of ANSI C12.1(2001), the national standard for watthour meters that applies to all the utility companies in the country. 

Click on picture for larger view, then use browser's Back button to return here.

2411
2411 Meter

4720-4-1
Solid-Core CT

4735-1

Small Split-Core CT

4725-2

Large Split-Core CT
4921-1

Sealed Counter
4923-1

Unsealed Counter

Glacier Electronics Module Specifications
Voltage Requirements: 90-140 VAC Line to Neutral, 180-280 VAC Line to Line Physical Size: 5.0" x 2.78" x 0.91"
Frequency: 50-60 Hz Weight: 4.0 oz stand-alone, 4.3 oz Plus models
Power Consumption: less than 2 watts for stand-alone meters
less than 3 watts for Plus and Plus IO models
Operating Temp:
Note:
-20°F to 160°F (-28.8°C to 71.1°C)
Display counter range is smaller. See below.
Phase: Single phase Storage Temp: -40°F to 160°F (-40°C to 71.1°C)
Elements: One Humidity: Non-Condensing


Solid-Core Current Transformer Specifications
Model 4720/4  
Outside Diameter: 2.1" Turns Ratio: 400:1
Inside Diameter: 0.9" Burden Resistor: None - on circuit board
Weight 2.5 oz. Leads: 24";, 18 ga., 300V insulation


Split-Core Current Transformer Specifications
Model 4735/1  
Outside dimension: 3.3" x 2.2" Turns Ratio: 3000:1
Inside Dimemension: Burden resistor None - on circuit board
Weight: 12.4 oz. Leads: 68", 18 ga, 600V insulation
Model 4735/2  
Outside dimension: 4.5" x 4.2" Turns Ratio: 3000:1
Inside Dimemension: Burden resistor None - on circuit board
Weight: 22.2 oz. Leads: 68", 18 ga, 600V insulation


Electro-Mechanical Display Specifications
Sealed Counters  
Counter model: Kubler K46.20/K47.20 Panel Cutout: 1.06" x 0.55"
Operating Temp: 14°F (-10°C) - 140°F (60°C) Reset: None
Max dist from meter: 20 ft. for 12V counters
300 ft for 6V counters
Digits: 6 for 1.0 kwh and 0.1 kwh resolution
7 for 0.01 kwh resolution
  Wires to counters must be installed in conduit Digits for units are white, digits for tenths and hundredths are red


Glacier Part Numbering Guide
2 X 1 Y / Z  
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
  Z Part Number Suffix - Add values of desired features
0Solid Core CTs, 0.1 kwh resolution
150 ms pulse output when "X" =
1Twisted Pair Interrface for Plus IO meters
2KYZ pulse output when "X" =
23 multi-purpose IO ports for Plus IO meters
4Designates bi-directional Everglades Meter
81.0 kwh resolution
16Not used with this meter
320.01 kwh resolution
64Split-core CTs
1281 wh resolution available
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Y
0200 amp max
1100 amp max
320 amp max
5500 amp max
61500 amp max
7750 amp max
81000 amp max
| | 1 One Counter Driver
|
|
|
X
4Single-Element, Stand-Alone Meter
5Single-Element, Computer-Readable Meter (Plus or Plus IO)
2Two Wire, 208-240 Volts Line to Line

Example: 2411 means a Glacier meter, Two Wire, 208-240 Volts Line to Line, single-element, stand-alone, one counter driver, 100 amps maximum, 0.1 kwh resolution, solid-core CT (Glacier 100)